Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Item Number
D226323
Catalogue No.
BTKM42V315
Item Description (ERP)
315B3X
Short Description
Central Bolted Tag fuse-links gG BTKM 415VAC/240VDC 315A
EAN/UPC Code
3605340268003
Rated voltage AC IEC
415 V
Rated voltage DC IEC
240 V
Ampere Rating
315 A
Speed/Characteristic
gG
Mounting
Bolted
Clearing I2t At Rated Voltage
756000 A²s
Melting I2t
270000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
31 W
Connection/Terminal Material
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
0.75 lb
Product Diameter
1.65 in
Product Width
0 in
Product Length
6.26 in
Sell Pack Quantity
1 EACH
Sell Pack Weight
0.75 lb
Sell Pack Width
1.97 in
Sell Pack Length
6.3 in
Sell Pack Height
1.69 in