Approvals & Standards
Key features & benefits
The NH system is classified among plug-in fuse systems and is composed of:
Type "gG" NH fuse-links are full range breaking capacity fuse-links and are used to protect cables and equipment. They can interrupt any current surge, from the lowest fusing current up to their breaking capacity, and so can be used alone as protection. They also protect electrical devices and industrial set-ups from the electrodynamic effects of very high short-circuit currents.
More specificationsApplications
Documents & Resources
Datasheet
Compliance
Item Number
D213995
Catalogue No.
NH000GG50V6
Description
DIN NH Standard fuse-link gG Size NH000 500VAC 250VDC 6A live tags Double indicator Body width 21mm
EAN/UPC Code
4086500083022
Rated voltage AC IEC
500 V
Rated voltage DC IEC
250 V
Ampere Rating
6 A
ROHS Compliant
Yes
AC or DC
AC/DC
Speed/Characteristic
gG
Fuse Size
NH000
Mounting
Clip
AC Max I.R./Breaking Capacity: I1
120 kA
Power Dissipation at Rated Current Value
1.6 W
Design Details
live tags
Indication System
Yes
Indication System Type
Double indicator
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Plain Blades
Body/Insulating Material
Ceramic
Product Weight
0.2866 lb
Product Width
0.83 in
Product Length
3.09 in
Product Height
2.07 in
Sell Pack Quantity
3 EA
Sell Pack Weight
0.8598 lb
Sell Pack Width
3.27 in
Sell Pack Length
2.76 in
Sell Pack Height
2.40 in