Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Documents & Resources
Compliance
Item Number
C1019201
Catalogue No.
BTSD42V63M100
Description
British Standard fuse-link IEC BS88 gM Type A4 415VAC 240VDC 63M100A BTSD Offset Tag
EAN/UPC Code
3605340515589
Rated voltage AC IEC
415 V
Rated voltage DC IEC
240 V
In M Ich
63M100 A
Speed/Characteristic
gM
Mounting
Bolted
Clearing I2t At Rated Voltage
65000 A²s
Melting I2t
14000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
4.7 W
Connection/Terminal Material
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
0.132 lb
Product Diameter
0.83 in
Product Width
0.96 in
Product Length
4.33 in
Sell Pack Quantity
10 EACH
Sell Pack Weight
1.323 lb
Sell Pack Width
4.61 in
Sell Pack Length
8.58 in
Sell Pack Height
1.5 in