Approvals & Standards
Key features & benefits
Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They are single, double, triple or quadruple barrels 3 inch diameter (size D) with end mounts designed for bolting directly to equipment bus or terminal pads.
More specificationsApplications
Documents & Resources
Datasheet
Drawings
Curves
Item Number
A083B2DAR0-175E
Description
Medium Voltage E-Rated Fuse 8250VAC 175A Bolt-On, Series: DAR0 Visual Indicator Amp-Trap®
EAN/UPC Code
782001302757
Rated voltage AC UL
8250 V
Frequency
50/60 Hz
Ampere Rating
175 A
AC or DC
AC
Speed/Characteristic
E-Rated
Mounting
Bolted
AC Max I.R./Breaking Capacity: I1
50 kA
Indication System
Yes
Indication System Type
Visual Indicator
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Blade
Body/Insulating Material
GMG
Comments
DAR0
Product Weight
22.1 lb
Product Width
3 in
Product Length
19.25 in
Product Height
7.63 in
Sell Pack Quantity
1 EA
Sell Pack Weight
23.21 lb
Sell Pack Width
7.62 in
Sell Pack Length
19.38 in
Sell Pack Height
3.12 in