Approvals & Standards
Key features & benefits
Mersen fuses for the protection of transformers and distribution lines deliver overload and short circuit protection. These current-limiting fuses will melt at current that can be as low as 1.7 times the fuse current ratings up to its maximum interrupting rating. These fuses are designed to withstand the transformer magnetizing inrush current. They are single, double, triple or quadruple barrels 3 inch diameter (size D) with end mounts designed for bolting directly to equipment bus or terminal pads.
More specificationsApplications
Documents & Resources
Datasheet
Drawings
Curves
Item Number
A055B1DAR0-200E
Description
Medium Voltage E-Rated Fuse 5500VAC 200A Bolt-On, Series: DAR0 Visual Indicator Amp-Trap®
EAN/UPC Code
782001309503
Rated voltage AC UL
5500 V
Frequency
50/60 Hz
Ampere Rating
200 A
AC or DC
AC
Speed/Characteristic
E-Rated
Mounting
Bolted
AC Max I.R./Breaking Capacity: I1
63 kA
Indication System
Yes
Indication System Type
Visual Indicator
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Bolted
Body/Insulating Material
GMG
Comments
DAR0
Product Weight
12.1 lb
Product Diameter
3 in
Product Length
19.25 in
Sell Pack Quantity
1 EA
Sell Pack Weight
12.71 lb
Sell Pack Width
5.5 in
Sell Pack Length
28.12 in
Sell Pack Height
4.5 in