Approvals & Standards
Key features & benefits
STP T2 40 is the series of Type 2/Class II devices for discharging
voltage surges, in accordance with EN/IEC 61643-11 and certified UL
1449 4th Ed. Suitable for the second stage of protection in supply
distribution panels in which Type 1 protection devices are installed
upstream, or for the first stage of protection in commercial or other
applications not exposed to direct strikes and with no external
lightning protection system.
Applications
Documents & Resources
Datasheet
Compliance
Item Number
83020106
Catalogue No.
STPT2-40K275V-1P
Item Description (ERP)
STPT2-40K275V-1P
Short Description
SPD Type 2, 40kA, Uc275V, L-N, 1 Pole, 1 Module, Pluggable
EAN/UPC Code
8435297850595
ROHS Compliant
Yes
IEC SPD Type
Type 2 / Class II
Format
Pluggable
Nominal Operating Volt Rating (Un)
230 V
AC or DC
AC
Nominal Discharge Current (In) (8/20)
20kA
Max Discharge Current : Imax (8/20)
40kA
System Configuration
TT. TNS. TNC. IT
Short Circuit Current Rating (SCCR)
50 ... 100 kA
Short Circuit Withstand (ISCCR)
25 kA
Indication System
Yes
Indication System Type
Visual Indicator
Number of Poles
1-Pole
Torque Rating
35.403 lb-in
Max. Back-Up Fuse
125 A gG
Housing Material
PA66 CT1; V-0
MOV Response Time
25 ns
Uc (L-N)
275 V
Up at In (L-N)
≤1.3 kV
MCOV L-L
275
VPR L-L
900 V
Replacement Plug L-N
SP2-40K275V
Product Weight
0.295 lb
Product Width
0.71 in
Product Length
2.76 in
Product Height
3.54 in
Sell Pack Quantity
1 EA
Sell Pack Weight
0.295 lb
Sell Pack Width
0.91 in
Sell Pack Length
4.13 in
Sell Pack Height
3.15 in