Approvals & Standards

  • UL Listed to Standard 248-9 File E2137
  • CSA Certified to Standard C22.2 No. 248.9 (The Canadian Electrical Code requires these fuses in ratings 15 through 60A to be of the low melting point design; use OTN 15-60.)
  • Self-certified for DC per UL248

Key features & benefits

One-Time OTS general purpose fuses provide low cost protection for feeder and branch-circuits serving lighting, heating, and other non-motor loads. OTS fuses will safely interrupt available short circuit currents up to 50,000 amperes in all ratings. OTS fuses are not rejection fuses and care should be taken to ensure that replacement fuses do not have lower interrupting ratings than original fuses.

More specifications

Applications

  • Feeders
  • Branch circuits
  • Resistive heating
  • Residential and small commercial installations

Product Specifications

Item number

OTS200  

Description

Fusible OTS - Clase K5 – Acción rápida 600VAC 300VDC 200A Cuchilla Amp-Trap®  

EAN/UPC Code

782001700966  

Rated voltage AC UL

600   V

Rated voltage DC UL

300   V

Ampere Rating

200   A

ROHS Compliant

Si  

Fuse Class

Class K5  

Speed/Characteristic

Fast-Acting  

Mounting

Clip  

AC Max I.R./Breaking Capacity: I1

50   kA

Connection/Terminal Material

Tin-Plated Copper  

Connection/Terminal Type

Blade  

Body/Insulating Material

PolyTube  

Product Weight

1.54   lb

Product Diameter

1.81   in

Product Length

9.63   in

Sell Pack Quantity

1   Each

Sell Pack Weight

1.62   lb

Sell Pack Width

1.94   in

Sell Pack Length

1.94   in

Sell Pack Height

10   in