Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Item number
W1066276
Catalogue No.
BTC42V200
Short Description
Central Bolted Tag fuse-links gG BTC 415VAC/240VDC 200A
EAN/UPC Code
3605340607802
Rated voltage AC IEC
415 V
Rated voltage DC IEC
240 V
Ampere Rating
200 A
Speed/Characteristic
gG
Mounting
Bolted
Clearing I2t At Rated Voltage
293000 A²s
Melting I2t
105000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
16.2 W
Connection/Terminal Material
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
0.265 lb
Product Diameter
1.22 in
Product Length
5.35 in
Sell Pack Quantity
5 EACH
Sell Pack Weight
1.323 lb
Sell Pack Height
0 in