Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Documents & Resources
Compliance
Item number
T1006612
Catalogue No.
BTCP69V100
Description
Fusible estándar británico IEC BS88 gG Tipo A4 690VAC 460VDC 100A BTCP Cuchillas compensadas
EAN/UPC Code
3605340536775
Rated voltage AC IEC
690 V
Rated voltage DC IEC
460 V
Ampere Rating
100 A
Speed/Characteristic
gG
Mounting
Bolted
Clearing I2t At Rated Voltage
80000 A²s
Melting I2t
14000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
7.5 W
Connection/Terminal Material
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
0.249 lb
Product Diameter
1.06 in
Product Width
1.12 in
Product Length
4.37 in
Sell Pack Quantity
10 EACH
Sell Pack Weight
2.491 lb
Sell Pack Width
5.12 in
Sell Pack Length
9.06 in
Sell Pack Height
1.57 in