Approvals & Standards
EN 60269-2 section II
Key features & benefits
The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” motor protection (gM type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.
More specificationsApplications
Item number
H1006625
Catalogue No.
BTF69V125M200
Description
Fusible estándar británico IEC BS88 gM Tipo B2 690VAC 460VDC 125M200A BTF atornillado
EAN/UPC Code
3605340485103
Rated voltage AC IEC
690 V
Rated voltage DC IEC
460 V
In M Ich
125M200 A
Speed/Characteristic
gM
Mounting
Bolted
Clearing I2t At Rated Voltage
350000 A²s
Melting I2t
105000 A²s
AC Max I.R./Breaking Capacity: I1
80 kA
Power Dissipation at Rated Current Value
10.1 W
Connection/Terminal Material
Tin-Plated Copper
Connection/Terminal Type
Slotted Blades
Product Weight
0.686 lb
Product Diameter
1.65 in
Product Width
0 in
Product Length
5.43 in
Sell Pack Quantity
5 EACH
Sell Pack Weight
3.428 lb
Sell Pack Width
5.71 in
Sell Pack Length
9.65 in
Sell Pack Height
3.35 in