Approvals & Standards
IEC 60282-1
Key features & benefits
Mersen HV fuse-links have been used for reliable protection in high-voltage switchgear and controlgear and high-voltage systems for decades.
Limitor®-G HV fuses are general purpose fuses as defined in the IEC 60282-1 standard and dedicated to protect transformers against effects of short-circuit currents and low overcurrents.
To guarantee high quality, Mersen uses the best materials: fuse-elements are in pure silver, caps are in copper coated with silver and bodies are in ceramic.
Applications
HV Transformer protection
Item number
E1000159
Catalogue No.
45DG240V10P
Description
Fusible de uso general DIN de media tensión para transformador Limitor® 24kVAC CEI 10A d78mm, L442mm Con Percutor 80N
EAN/UPC Code
3605340453324
Rated voltage AC IEC
24 kV
Ampere Rating
10 A
Fuse Size
d=78mm, L=442mm
Mounting
Clip
Clearing I2t At Rated Voltage
3.6 kA²s
AC Max I.R./Breaking Capacity: I1
40 kA
Min Interrupting Rating (MBC)
0
Power Dissipation at Rated Current Value
15 W
Indication System
Si
Indication System Type
Striker
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Cylindrical
Body/Insulating Material
Ceramic
Product Weight
9.039 lb
Product Diameter
3.07 in
Product Length
20 in
Sell Pack Quantity
1 EACH
Sell Pack Weight
9.039 lb
Sell Pack Width
3.54 in
Sell Pack Length
21.65 in
Sell Pack Height
3.94 in