Pasar al contenido principal

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International website
Country / Language:  USA / Spanish
Contact us

Approvals & Standards

EN 60269-2 section II

Key features & benefits

The fuse complies with standard EN 60269-2 section II and standard BS 88 part 2. These fuses are designed for : “General purpose use” protection (gG type). This fuse range insures an excellent current limitation for all overloads on a large range of applications. Their size cannot allow exchange by other fuses of higher rating in their range. They are screwed into fuseholders or bolted directly onto busbars, or in fuse interruptors disconnectors.

More specifications

Applications

  • These fuses are designed for : “General purpose use” protection (gG type)

Product Specifications

Item number

D1006621  

Catalogue No.

BTF69V125  

Description

Fusible estándar británico IEC BS88 gG Tipo B2 690VAC 460VDC 125A BTF atornillado  

EAN/UPC Code

3605340485066  

Rated voltage AC IEC

690   V

Rated voltage DC IEC

460   V

Ampere Rating

125   A

Speed/Characteristic

gG  

Mounting

Bolted  

Clearing I2t At Rated Voltage

140000   A²s

Melting I2t

28000   A²s

AC Max I.R./Breaking Capacity: I1

80   kA

Power Dissipation at Rated Current Value

11.3   W

Connection/Terminal Material

Tin-Plated Copper  

Connection/Terminal Type

Slotted Blades  

Product Weight

0.689   lb

Product Diameter

1.65   in

Product Width

0   in

Product Length

5.43   in

Sell Pack Quantity

5   EACH

Sell Pack Weight

3.445   lb

Sell Pack Width

5.71   in

Sell Pack Length

9.65   in

Sell Pack Height

3.35   in