Key features & benefits
Fuse supports, fuse disconnect switches and accessories from 2.4kV to 38kV
Fuse supports, non-disconnecting, are used primarily in potential transformer circuits, or where there is some other disconnecting or isolating device in series with the fuse in the circuit. Disconnecting switch devices have the additional feature of serving to isolate the equipment they protect. It should be noted that disconnecting switches are not load-breaking devices, therefore, the circuit must be open prior to the fuse disconnection. Select either a fuse support or a disconnecting switch for each fuse. Fuse supports and disconnecting switches include live parts for both ends. Both fuse supports and fuse disconnect switches can be mounted vertically or horizontally. The type EK are used for indoor installations while the type EKO are used outdoors.
More specificationsItem number
9F61AEB401
Short Description
9F61 EK-1 Indoor Support 5.5 kV 60 kV 2x3 inch long
EAN/UPC Code
782001400033
Rated voltage AC UL
5.5 kV
ROHS Compliant
Si
Fuse Size
2x3in
Design Details
Long
Number of Poles
1-Pole
Body/Insulating Material
Fiberglass Reinforced Polyester
Installation Mounting
Tornillo
BIL
60 kV
Comments
2x3
Product Weight
30 lb
Product Width
6 in
Product Length
21.92 in
Product Height
12 in
Sell Pack Quantity
1 EA
Sell Pack Weight
31.5 lb
Sell Pack Width
18 in
Sell Pack Length
29 in
Sell Pack Height
9 in