Approvals & Standards
A4BQ (100-6000)
Key features & benefits
Amp-Trap 2000 A4BQ fuses are 20 percent more current limiting than any other Class L fuse on the market. When correctly coordinated, they bring a superior level of protection to service entrance equipment. Downstream circuit components have maximum protection against short circuit let-thru current. A4BQ's built-in 4-second time-delay characteristic (at 500percent of rated current) accommodates harmless inrush currents with no nuisance opening.
More specificationsApplications
Documents & Resources
Datasheet
Drawings
Curves
Compliance
Item Number
A4BQ450
Description
Fuse A4BQ - Class L - Time-Delay 600VAC 500VDC 450A Blade Amp-Trap 2000®
EAN/UPC Code
782001930691
Rated voltage AC UL
600 V
Rated voltage DC UL
500 V
Ampere Rating
450 A
ROHS Compliant
Yes
Fuse Class
Class L
Speed/Characteristic
Time Delay
Mounting
Bolted
AC Max I.R./Breaking Capacity: I1
200 kA
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Blade
Body/Insulating Material
GMG
Product Weight
2.6 lb
Product Diameter
2 in
Product Length
8.63 in
Sell Pack Quantity
1 Each
Sell Pack Weight
2.73 lb
Sell Pack Width
2.12 in
Sell Pack Length
2.12 in
Sell Pack Height
8.81 in