Skip to main content

All locations

Please select your country & language

China | 中国
Germany | Deutschland

Your country is not in the list?

Go to our international website:

Mersen EP International website
Country / Language:  USA / English
Contact us

Approvals & Standards

  • IEC 60269-7
  • RoHS compliance

Key features & benefits

Mersen NH gBat fuse series was engineered specifically for protection
of battery systems. They offer full range protection and can protect
very small over currents as well as DC fault current up to 150kA. The
NH gBat fuses serie covers various ratings in 1000VDC with NH1 and
NH2 sizes, and in 1500VDC with NH1XL, NH2XL and NH3L sizes. They are gBat type that comply with new IEC 60269-7 standard for Battery protection. They are available with bolted type blades for
direct mounting, or with plain blades.

More specifications

Applications

  • Electrical energy storage
  • Battery storage system
  • Line protection between battery system and DC/DC converter or battery inverter
  • DC grid protection

Product Specifications

Voltage Range

1000V...1500V DC  

Ampere Range

50 ... 500 A  

Speed/Characteristic

gBAT  

CE Conformity

Yes  

Max Operating Temp.

70   °C

Min Operating Temp.

-40   °C

References in this series  (50)

Y1068647 - 15NH2XLGBAT250B

250   A

2XL  

-

No

2.249   lb

Y1204048 - 15NH3LGBAT450

450   A

3L  

-

No

4.365   lb

Z1068625 - 10NH1GBAT160

160   A

NH1  

-

No

0.661   lb

Z1068648 - 15NH3LGBAT160

160   A

3L  

-

No

3.726   lb

Z1204049 - 15NH3LGBAT500

500   A

3L  

-

No

4.365   lb