Approvals & Standards
AJT (1-600):
AJT (70-600) EI:
Key features & benefits
Amp-Trap 2000® AJT fuses provide non-indication as well as a SmartSpot visual open fuse indicator. With advanced material technology the AJT fuse provides IEC Type 2 No Damage protection to main, feeder, and branch circuits, for all types of loads — yet, they require only half the mounting space needed for 600VAC Class RK fuses. AJT’s time-delay characteristics are ideal for handling typical motor and transformer inrush currents, while also providing superior current-limiting ability.
More specificationsApplications
Documents & Resources
Datasheet
Drawings
Curves
Compliance
Item Number
AJT100N
Description
Fuse AJT - Class J - Time-delay 600VAC 400VDC 100A Blade Amp-Trap 2000®
EAN/UPC Code
782001497828
Rated voltage AC UL
600 V
Rated voltage DC UL
400 V
Frequency
50/60 Hz
Ampere Rating
100 A
ROHS Compliant
Yes
Fuse Class
Class J
Speed/Characteristic
Time Delay
Mounting
Clip or Bolted
AC Max I.R./Breaking Capacity: I1
200 kA
Connection/Terminal Material
Silver-Plated Copper
Connection/Terminal Type
Blade
Body/Insulating Material
GMG
Product Weight
0.28 lb
Product Diameter
1.063 in
Product Length
4.63 in
Sell Pack Quantity
5 Each
Sell Pack Weight
1.47 lb
Sell Pack Width
5.38 in
Sell Pack Length
6.00 in
Sell Pack Height
1.06 in