NH fuse-links gTr 400VAC middle indicator/live gripping-lugs size 2, 3, 4a

The NH system is classified among plug-in fuse systems and is composed of: • fuse-base, (possibly including terminal covers and phase barriers) • fuse-link with blade contact • fuse-link replacement device (LV HRC fuse puller) Since the design of this system cannot guarantee non-interchangeability of rated current, it must be handled by a qualified professional. NH-fuse links „gTr“ are used for the protection of transformers. The time/current characteristic is especially adapted to that of the protected transformer and implies optimal selectivity to NH-fuse links characteristic gG. The fuses can be loaded with 1,3 times nominal current for up to 10 hours. The fuse link operates at 1,5 times nominal transformer current within 2 hours.

 

FEATURES

  • Maximum transformer capacity (up to 1,3 x In)
  • Reduction of unnecessary interruption of operation
  • Precise cut off of overload
  • Characteristic adapted to the transformer
  • Resistant to ageing
  • Selectivity to fuse links gG
  • High current limiting
  • High breaking capacity
  • Easy selection between transformer and fuse link
 

PRODUCT DETAILS

  • Volts (VAC) 400 VAC
  • Ampere Range (A) 72 - 1443 A
  • I.R. AC (kA) 100 kA
  • Size per Standard Sizes 2
    3
    4a
  • Speed / Characteristic gTr
  • Body Material Ceramic
  • Materials Contact Copper
    Silver-plated
  • Standards VDE 0636 Part 201
    IEC 60269-1 and -2
  • Application Protection of transformers
  • ROHS Compliant Consult Technical Services
  • Lead Free Consult Technical Services
  • CE conformity Yes
 

Catalog-Reference

  • NH22GTR200KVA - G1030498
  • NH22GTR250KVA - H1030499
  • NH2GTR100KVA - V1028693
  • NH2GTR125KVA - W1028694
  • NH2GTR160KVA - Y1028696
  • NH2GTR50KVA - S1028691
  • NH2GTR75KVA - T1028692
  • NH32GTR315KVA - Y1030513
  • NH32GTR400KVA - Z1030514
  • NH32GTR500KVA - H1028705
  • NH32GTR630KVA - A1030515
  • NH3GTR100KVA - L1030502
  • NH3GTR125KVA - J1028706
  • NH3GTR160KVA - M1030503
  • NH3GTR200KVA - N1030504
  • NH3GTR50KVA - J1030500
  • NH3GTR75KVA - K1030501
  • NH4A2GTR1000KVA - L1030525
  • NH4A2GTR500KVA - H1030522
  • NH4A2GTR630KVA - J1030523
  • NH4A2GTR800KVA - K1030524
  • NH4AGTR100KVA - X1028718
  • NH4AGTR125KVA - Y1028719
  • NH4AGTR160KVA - Z1028720
  • NH4AGTR200KVA - A1028721
  • NH4AGTR250KVA - B1028722
  • NH4AGTR315KVA - C1028723
  • NH4AGTR400KVA - D1028724
 

CAD & OUTLINE DRAWINGS

  • CAD Drawings

    • Drawing 1000412_C_NHC2 SFU :   PDF (298 KB)

Back

Find what you need fast...


Quick Links


Where to buy

ZIPCODE:

© 2017 Mersen S.A. All rights reserved.