Catalog

Engineered Panels

Fused Coordination Panelboard

Fused Coordination Panelboards

Mersen’s Fused Coordination Panelboard is designed to meet requirements defined by the National Electrical Code (NEC) to protect critical power operations. These panels are provided with a default short circuit current rating (SCCR) of 200kA and provide overcurrent protection through a combination of a circuit breaker and a fuse. The circuit breaker is designed to operate on overloads up to 2 times their rating and the fuse over 2 times up to 200kA. Mersen’s Fused Coordination Panelboard can simplify the process in achieving code compliance for designers.

 

FEATURES

  • Easy selectivity ratios with upstream fuses
  • Resettable overload protection
  • Voltage: 120/208, 120/240, 277/480, 347/600
  • Main Bus: 250A or 400A,
  • MLO, Fused Main or Non-fuse Main disconnect
  • SCCR: 200kA
  • Surge Protection (SPD) optional
  • 20, 32 or 42 branch circuits
  • Standard 20" wide
  • Feed through lugs optional
  • Surface mount
  • Uses commonly available class CC & J fuses
 

PRODUCT DETAILS

  • Voltage Range (VAC) 208-600 VAC
  • Ampere Range (A) Main Bus: 250-400 A
  • Number of Poles 1
    2
    3
  • ROHS Compliant Consult Technical Services
  • Lead Free Consult Technical Services
  • CE conformity Consult Technical Services
 