Catalog

High Voltage AC

High Frequency Disconnectors

Disconnectors MF range (0,5 to 3000 Hz) (1250 to 72 000Amp)

For more than 100 years, Mersen has been providing the market with safe, reliable and longer life time off-load disconnectors. These devices offer high performances and robustness for heavy duty requirements with very limited maintenance. Mersen offers one of the largest product ranges on the market and is the global leader. Mersen has a switch solution that will meet your unique needs. Our standard MF High Power Switches are rigorously engineered to meet your technical specifications. Operation : They can be operated manually or with an adapted motor (see list) up to 60.000 cycles. Phase to Phase distance, Signaling, Terminal Box or Locking system can be studied and customized. Maximum frequency up to 3.000Hz (above please consult) Indoor in a currentless state Ambient air should not exceed +40°C (otherwise please consult) Altitude should not exceed 1000 m Relative humidity should not exceed 95% List 1 following IEC 62271-1

 

FEATURES

  • No Load operation
  • Indoor Type - Non Magnetic and tropicalized equipment which can be installed in vertical or horizontal position
  • Change-over (2 or 3 positions) or disconnector configuration with 1 to 10 poles double sided and 12 poles single sided technology. Warning , when reversing, the isolation between terminals 1 and 2 is not ensured.
  • Mechanical endurance : 60.000 cycles minimum warrantied for a device maintained according to the maintenance recommendations.
  • Electrical contact by connecting plates and movable contacts silvered copper entirely non-magnetic
  • Pressure of each rivet ensured by an individual spring in stainless steel.
  • Temperature rise at nominal current is less than 65°K (with 40°C max. ambient temperature)
  • Visible break by direct seeing of the mobile silver-plated copper contacts.
  • Large isolation air and creepage path.
  • Easy connections to Copper busbar by bolting and self-supporting (Busbar must be sized to withstand the disconnector additionnal weight).
  • Self-cleaning blade contacts.
  • True opening and visible distance.
  • Ponctual temperature withstand without equipment damages 140°C.
  • Full customisation with :
  • - Manual (handle or gear box), motor, pneumatic drives operation
  • - Quantity of Auxilary switches, safety blocking magnet, locking devices
  • - Dimensions of the disconnector and Fittings/connexions to the busbar.
  • Fixing flange in duralinox.
 

PRODUCT DETAILS

  • Size per Standard Disconnectors MF 0
    5 to 3000Hz
  • Speed / Characteristic 3 to 20 seconds with motor operation (according to the device)
  • Number of Poles 10 poles single sided or 12 poles double sided technology
  • Standards IEC 60947-3 and IEC 60077-1
  • Application Isolation of installations with a dirty surrounding
    Dividing of a source towards 2 applications (ex. : 2 induction furnaces)
    Isolation of installations requiring a withstand to very high short-circuit currents
  • ROHS Compliant Consult Technical Services
  • Lead Free Consult Technical Services
  • CE conformity Yes
 

Catalog-Reference

  • MF 100 Double sided
  • MF 100 Single sided
  • MF 125 Double sided
  • MF 125 Single sided
  • MF 160 Double sided
  • MF 160 Single sided
  • MF 200 Double sided
  • MF 200 Single sided
  • MF 250 Double sided
  • MF 250 Single sided
  • MF 80 Single sided