7.2kV to 15.5kV BOLT-IN FUSES are mulitple barrel (3" diam.) with end mounts designed for bolting directly to equipment bus or terminal pads. Some are UL listed and the 9F62KED is suitable for outdoor use. The unique time-current characteristic of Ferraz Shawmut E-Rated fuses allows them to be closely sized to transformer full load rated current, as recommended by IEEE guidelines, without being affected by normal magnetizing inrush current. Bolt-in fuses are typically sized at transformer rated current of 133%, thereby providing superior overall protection.
Features
- Some parts UL Listed
- Bolt-in mounting for direct connection to bus or terminals
- Current Limiting for superior equipment protection
- Blown-fuse indicator gives positive identification of open fuse
- Non-venting for silent operation
- Metal Embossed Catalog Number and manufacturing date for lasting identification
- 9F62KED300 rated for outdoor use
Applications
- Protection for 7.2kV - 15.5kV transformers or distribution systems